PEOPLE ELE.
KYN□-12(8BK80)型户内金属铠装移开式开关设备
型号及其含义 Type and its meaning
K Y N □ - 12 / T □ - □
额定短路开断电流(kA)额定电流(A)弹簧操动机构额定电压(kV)设计序号户内移开式金属铠装
名词解释
4.1 工作位置:是指可移开部件在柜内的一种定位状态。在工件位置时,开关柜的主回路及辅助回均接通。4.2 试验位置:是指可移开部件在柜内的一种定位状态。在试验位置时,开关柜的辅助回路接通,但主回路断开,并且动、静触头被金属活门分隔。
4.3隔离位置:如果可移开部件在柜内试验位置再切断辅助回路,可移开部件就处于隔离位置。
The term explain
4.1Work position: it means that the movement part is at some position in the cabinet. At the work position, the switchcabinet’s main loop and secondary loop are all switched on.
4.2.Test position: it means that the movement part is at some position in the cabinet. At the test position, the switchcabinetХs secondary loop is switched on, but the main loop is cut off, and at the same time the contact terminal ofmovement, the contact terminal of steady are comparted by the metal active door.
4.3 Isolation position: it means that the movement part is at the test position and cutting off the secondary loop, so thatit is at the isolation position
性能特点
5.1 零部件少,重量轻,属于8BK系列。5.2 模块化设计,结构简单、紧凑、可靠。
5.3 移开式手车,通过丝杆机构驱动操作,无需升降操作小车。
5.4 联锁机构符合IEC和GB、DL标准,前门完全和机械联锁结构配合。5.5 操作时高压室门关闭,分合、接地、移动操作时极为安全。5.6可装国产高质量的真空断路器。
5.7 铆钉结构泄压通道,结构简单,故障时对运行操作人员安全可靠。5.8 防护等级高达IP4X。
5.9 适用于各种方案,可用作进线柜、出线柜、母线提升柜、PT柜等。5.10 横向绝缘和水平抽出式结构使开关柜易于左右扩展。
5.11 柜体采用普通钢板或进口敷铝锌板,外形美观,经济性好,使用于不同地区选用。
Capability and specialty
5.1The amount of parts is a few, the weight of the setting is small, the setting belongs to the 8BK series.5.2blocking design, the structure is simple, fast, reliable.
5.3withdrawing handlebar, operated by thread pole organ drive, not need ascending-dropping vehicle.
www.peoplesbd.com160
PDF 文件使用 \"pdfFactory Pro\" 试用版本创建 www.fineprint.cnwww.peoplesbd.com161
PEOPLE ELE.
KYN□-12(8BK80)型户内金属铠装移开式开关设备
6.2 busbar room
the busbar room including: main busbar, branch busbar, insulation sleeve, over contact terminal capouch of insulationThe main busbar is extending busbar running through each switch cabinet, the twain end of the border busbar is fixedby bolts on the amphend connector, the amphend connector is fixed on the insulation part made of epoxy irrigating.6.3 cable room
Cable room including: below contact terminal capouch of insulation, cable connector, part of the main earthingbusbar, current mutual inductor, the switch of earthing. The cable room’s bottom floor structure makes the builder fixingcable more convenient.The amphend connector is visible from the back.6.4 instrument room
All of the instrument component (protection relay, amphend connector, indicated lamp, etc.) is fixed in the instrumentroom. The indicated lamp and relay is fixed in the beforehand fixing pole on the instrument door.
图1 开关柜结构示意图
6.5联锁unite lock
状 态下述操作不可能实现-打开高压门手车在工作位置-操作接地开关-拔出二次插头手车在工件位置,开关装置合闸-移动手车-开关装置合闸手车在试验和工作位置的中间时-打开高压门-拔出二次插头手车在试验位置,开关装置合闸拔出手车二次插头高压门开启-移动手车-关闭高压门-移动手车开关柜外形尺寸 The switch cabinet figure dimension
电 压3.6-12kV额定电流630-3150AW800h2200h12000d1380d1750d11750d11816注:1、在整个排列的左右端柜装有侧板。 2、电缆室的压力释放通道的深度110mm.Noted: 1. it is fixed flanking board at the all arraying left and right end of t he cabinet. 2. the cable rooms pressure releasing way is 110 mm depth.
www.peoplesbd.com162
PDF 文件使用 \"pdfFactory Pro\" 试用版本创建 www.fineprint.cnwww.peoplesbd.com163
PEOPLE ELE.
KYN□-12(8BK80)型户内金属铠装移开式开关设备
主要技术参数Technology parameter
9.1 KYN□-12开关设备主要技术参数 KYN□-12 switch setting main technology parameter序号1项 目额定电压(kV) lmin工频耐受电压(有效值kV)2绝缘水平 雷电冲击耐受电压(峰值kV)345678额定频率(Hz)主母线额定电流(A)额定短路开断电流(kA)额定短路关合电流(kA)动稳定电流(kA)热稳定电流(kA)/持续时间(s)真空断路器机械寿命(次)防护等级接地开关对地及相间一次断口间对地及相间一次断口间技术参数7.2 1232 4236 4860 7570 85501250,1600,2000,2500,315025,31.5,4063,80,10063,80,10025/4,31.5/4,40/410000,300002000IP4X表1
9109.2 KYN□-12(F-C)开关设备主要技术参数 KYN□-12 (F-C) switch setting main technology parameter序号1项 目额定电压(kV)lmin工频耐受电压对地及相间一次断口间对地及相间一次断口间3.624264046技术参数7.232366070501242487585表2
2绝缘水平(有效值kV)雷电冲击耐受电压(峰值kV)34567891011121314额定频率(Hz)主母线额定电流(A)F-C回路额定电流(A)预期短路开断电流(kA)预期短路关合电流(kA)主母线4s热稳定电流(kA)主母线动稳定电流(kA)分支母线4s热稳定电流(kA)分支母线4s热稳定电流(kA)真空断路器机械寿命(次)防护等级外型尺寸(宽×深×高)mm接地开关630,1250,1600,2000,2500,3150100,160,2244010040100410按自身技术条件规定2000IP4X800×1816×2200www.peoplesbd.com164
PDF 文件使用 \"pdfFactory Pro\" 试用版本创建 www.fineprint.cnwww.peoplesbd.com165
PEOPLE ELE.
KYN□-12(8BK80)型户内金属铠装移开式开关设备
9.5 3TL61、3TL65型真空接触器主要技术参数
9.5 3TL61, 3TL65 type vacuum contactor’s main technology parameter序号12345678910111213141516绝缘水平项 目额定电压(kV)lmin工频耐受电压(有效值kV)雷电冲击耐受电压(峰值kV)额定频率频率(Hz)额定电流(A);+55℃/+80℃额定短路开断电流(A)额定短路关合电流(A)额定热稳定电流(kA)/持续时间(s)额定电容器电流(A)最大关合电容器电流(峰值kA)操作频率(次/h)机械寿命(次)电气寿命(次)线圈合闸功率(W)/保持功率(W)操作电压范围合闸时间(ms/Uc)分闸时间(ms/Uc)对地、相间断口对地、相间断口技术参数3TL61 3TL657.2 1220 2860 7540 6050/60450/315360045008/1250101200 6002×106 1×1061×106 0.5×106650/900.8-1.1Uc100/0.85; 80/1.0; 60/1.130/0.8; 50/1.0; 50/1.1表5
9.6 JCZ5系列真空接触器主要技术参数
9.6 JCZ5 series vacuum contactor’s main technology parameter序号123456789101112131415161718192021电寿命(次)绝缘水平项 目额定电压(kV)额定电流(A)额定关合电流(A)最大额定开断电流(A)lmin工频耐受电压(有效值kV)雷电冲击耐受电压(峰值kV)额定短路开断电流(kA)额定短路关合电流(峰值kA)4s热稳定电流(kA)额定峰值耐受电流(kA)额定操作电压(V)额定操作频率(次/h)机械寿命(次)AC-3AC-4触头开距(mm)超程(mm)触头合闸弹跳时间(ms)平均合闸速度(m/s)平均分闸速度(m/s)合闸时间(ms)固有分闸时间(ms)外形尺寸(mm) 技术参数 JCZ5-3.6 JCZ5-7.2 JCZ5-12 3.6 7.2 12 250 400 400 2500 4000 4000 2000 3200 3200 23 32 42 40 60 75 4 4 4 10 10 10 4 4 4 10 10 10 110/220 110/220 110/220 300 300 300 30×104 30×104 30×104 25×104 25×104 25×104 10×104 10×104 10×104 3.5±0.5 4+1-0.5 6+1-0.5 1.5±0.5 1.5±0.5 1.5±00.1 ≤5 ≤5 ≤5 01.5±0.05 01.5±0.05 0.2±0.1 0.35±0.05 0.45±0.15 0.45±0.15 ≤100 ≤150 ≤150 ≤50 ≤50 ≤50355×353×190 400×240×400 502×300×450表6
www.peoplesbd.com166
PDF 文件使用 \"pdfFactory Pro\" 试用版本创建 www.fineprint.cnwww.peoplesbd.com167
PEOPLE ELE.
KYN□-12(8BK80)型户内金属铠装移开式开关设备
9.8.2 LZZBJ9-10/150、LZZBJ18-10/150型动热稳定电流
9.8.2 LZZBJ9-10/150、LZZBJ18-10/150 type dynamic heat endurance current
额定一次电流A IS热稳定电流(kA) 动稳定电流(kA) 准确级组合(1K/2K) 额定二次输出510152030405075100-200300-600800-12501500-315024.56.39.512.6182236507280100511152331.5455580901001101300.2/10P0.2S/10P0.5/10P0.5S/10P 10 10 10 10 15 0.2s 0.5s 0.2级 0.5级 10P级表10
9.8.3 LZZBJ9-10/185h/2、LZZBJ18-10/185/2型准确级次组合及相应的二次输出
9.8.3 LZZBJ9-10/185h/2、LZZBJ18-10/185h/2 type exact degree combination and correspond secondary output表11
额定二次输出20-500A600-2500A准确级次组合0.2/0.2;10P10/10P100.2/0.5;10P15/10P150.2/10P10;0.2/10P150.5/10P10;0.5/10P150.2/0.2/0.2;0.2/0.5/0.50.5/0.5/0.5;10P10/10P150.2/0.5/10P100.2/0.5/10P150.20.510P1010P150.20.510P1010P151520151520201510152015152030201015151015152015101515101520159.8.4 LZZBJ9-10/185、LZZBJ18-10/185型动热稳定电流
9.8.4 LZZBJ9-10/185,LZZBJ18-10/185 type dynamic heat endurance current额定一次电流AIs热稳定电流(kA)动稳定电流(kA)10-40200Iin500Iin50-100250Iin625Iin150-30045100400-500100250600-1000140350表12
1200-16002000-31501704252406009.9电压互感器主要技术参数
9.9 Voltage mutual inductor main technology parameter9.9.1 JDZ8-10、JDZ18-10系列电压互感器主要技术参数
9.9.1 KDZ8-10.KDZ18-10 series voltage mutual inductor main technology parameter
额定电压比(V/V)0.2极6000/10010000/10015额定输出(VA)0.5极301极603极150极限输出(VA)200表13
额定绝缘水表面爬电距平(kV)7.2/32/6012/42/75离(mm)210www.peoplesbd.com168
PDF 文件使用 \"pdfFactory Pro\" 试用版本创建 www.fineprint.cnwww.peoplesbd.com169
PEOPLE ELE.
KYN□-12(8BK80)型户内金属铠装移开式开关设备
9.12 LXK-φ120型零序电流互感器配用继电器主要技术参数说明: 电缆出线柜可根据用户需要配零序电流互感器。一般配用LXK-φ120型零序电流互感器(最大穿过电缆直径φ120mm)。9.12 LXK-F120 type zero sequence current mutual inductor assorting relay main technology parameter
notice: the cable room is assorted with zero sequence current mutual inductor according to the user need. In general,it is assorting with LXK-F120 type zero sequence current mutual inductor (maximal diameter of cable is 120mm.)表18继电器型号继电器线圈连接方式串联DD-11/60并联串联DD-1/60并联继电器刻度值15×130×115×130×115×130×115×130×13-63-53-52.4-4.5一次零序电流值(A)9.13 HY5WS1 型复合绝缘氧化锌避雷主要技术参数
9.13 HY5WS1 type complicated insulation zinc oxide lightning protector抯 main technology parameter
产品型号HY5WS1-7.6/30HY5WS1-12.7/50HY5WZ1-7.6/27HY5WZ1-12.7/45HY5WR1-7.6/27HY5WR1-12.7/45HY2.5WD1-7.6-19HY2.5WD1-12.7/31HY5WS1-10/30HY5WS1-17/50HY5WZ1-10/27HY5WZ1-17/45HY5WR1-10/27HY5WR1-17-45HY5WS1-16.5/50HY5WZ1-16.5/45HY5WS1-3.8/17HY5WZ1-3.8/13.5HY5WR1-5/13.5额定电压(kV)持续运行电压(kV)7.612.77.612.77.612.77.612.710171017101716.516.53.83.854.06.64.06.64.06.64.06.68.013.68.013.68.013.612.712.72.02.04.0表19
直流1mA参考电压(kV)8/20us标称电流下残压(kV)2ms方波通流容量(kA)4/10us冲击电流容量(kA)≥15.0≥25.0≥14.5≥24.0≥13.8≥23.0≥11.3≥18.9≥15.0≥25.0≥14.5≥24.0≥14.4≥24.0≥25.0≥24.0≥7.5≥7.2≥7.2≤30≤50≤27≤45≤27≤45≤19≤31≤30≤50≤27≤45≤27≤45≤50≤45≤17≤13.5≤13.510010015015040040020020010010015015040040015040065656565656540406565656565656565656565开关柜及母线的安装
10.1开关柜安装
10.1.1 开关柜运至现场,断路器手车应单独存放。
10.1.2 用吊车或铲车将开关柜运至安装位置,在柜与柜之间保持0.5m距离,以便于移动开关柜。较长的开关柜排列,拼柜工作应从中间部位开始。
10.1.3 在基础上一个接一个安装开关柜,包括水平和垂直两方向。
10.1.4 当开关柜已完全组合(拼接)好时,可用地脚螺钉将其与基础构架相联或用电焊与基础构架焊牢。10.2 母线的安装
10.2.1 用清洁干燥软布擦揩母线,检查绝缘套管有无损伤,在连接部位上涂导电膏或中性凡士林。10.2.2 安装好主母线后,将主母线和对应的分支母线接在一起,用内六角螺栓拧紧。10.2.3 套好连接处需要的绝缘套。